Every liquid-cooled rack sits on a secondary fluid network — the closed loop that carries coolant from the coolant distribution unit (CDU) through row and rack manifolds to the cold plates on the servers and back. Essem Works makes the stainless steel parts of that loop in its own works at Ahmedabad — the braided corrugated hose assemblies, the rack and row manifolds, the expansion joints on the chiller plant — and supplies the quick-disconnect couplings, valves and instruments the specification names, so a data centre, its MEP contractor or its CDU OEM can buy the network from the CDU to the cold plate as one tested, documented kit or as a skid.
What a secondary fluid network is
A liquid-cooled data centre has two water loops. The facility water system (FWS) runs from the chillers or dry coolers to the CDU. The secondary fluid network (SFN) — ASHRAE calls it the technology cooling system, TCS — runs from the CDU's heat exchanger and pumps to the IT equipment: supply and return pipework to a row manifold, a vertical rack manifold in each cabinet, and short flexible whips from the manifold to each server's cold plates through quick-disconnect couplings. The CDU hydraulically separates the two loops, so the coolant that touches the electronics — commonly a 25 % propylene glycol and water mixture, PG25 — is a small, controlled volume.
The duty is gentle on paper: a few bar, supply temperatures in the ASHRAE W17 to W45 classes (the number is the maximum supply temperature in °C to the equipment), no vibration to speak of. What makes it demanding is the consequence of a leak — coolant running centimetres from energised hardware whose replacement cost dwarfs the cooling loop, in a facility that is not allowed to stop. That is why the network is specified in stainless steel and why every joint in it should be tested before it reaches site.
What we supply for the SFN
| Element | What we supply | How |
|---|---|---|
| CDU connections — supply and return | 316L braided corrugated hose assemblies, DN25 to DN100, with flanged, grooved-coupling-ready or threaded ends to match the CDU and the header; single braid, ends welded, pneumatically leak-tested per piece | Made in our works |
| Row manifold to rack manifold | 316L braided corrugated hose assemblies, DN20 to DN50, sized so the installed bend radius is above the minimum with the connector engaged | Made in our works |
| Rack manifolds and row manifolds | Fabricated stainless manifolds in 304L or 316L to the rack's port count and pitch, TIG-welded branches, ports threaded to the coupling standard (BSPP, NPT or SAE O-ring boss), isolation and drain points, pressure tested and certified as a unit | Fabricated to drawing |
| Manifold-to-server whips | 316L braided corrugated hose, DN6 to DN20, in the lengths the rack layout needs, with the quick-disconnect coupling fitted and the assembly tested with it | Hose made in our works; coupling supplied |
| Quick-disconnect couplings | Couplings to the OCP Universal Quick Disconnect (UQD) interface — UQD02, UQD04, UQD06 and UQD08 (3.2, 6.4, 9.5 and 12.7 mm flow diameter, 10 bar maximum working pressure), and the blind-mate UQDB where the rack design uses it — in the brand the CDU or server OEM has qualified | Supplied to the specification |
| Isolation, balancing and drain valves; flow, temperature and pressure instruments; leak-detection points | Supplied and fitted to the manifold or skid as the specification names them | Supplied to the specification |
| Chiller plant, risers and headers | Axial and lateral expansion joints and pump connectors on the facility water side — the thermal movement and vibration of the primary loop, kept off the CDU | Made in our works |
| SFN skid | Row manifold, valves, instruments and drain and vent points mounted on a stainless frame, pipework tested as a unit, ready to connect to the CDU; the CDU itself and its pumps come from the OEM and the skid is built around their connections | Assembled and tested in our works |
The hose is never the limiting element. A DN25 single-braid assembly carries 50 kg/cm² at 20 °C on the ISO 10380 basis of our published table, and at SFN loop temperatures the derating is small but real — at 45 °C the 316L factor is about 0.89 on our table, so that DN25 whip still carries about 44 kg/cm². The coupling, at 10 bar, sets the working pressure of the whip, and we say so on the drawing.
Why the network is specified in stainless steel
It does not permeate
A metal wall passes no coolant vapour and absorbs no inhibitor. A polymer hose loses fluid slowly through its wall and the loop chemistry drifts with it; a stainless loop holds its fill.
It does not age out
No five-year replacement written into the operating procedure, no elastomer hardening behind a rack nobody wants to open again. The only maintenance item on a stainless whip is the coupling's seal.
316L for the chemistry
Make-up water, inhibitor packages and whatever was dosed last quarter put chlorides into warm water — the classic stress-corrosion recipe for 304L. We build the SFN in 316L, and the media compatibility page says where even that stops being enough.
One metal, or isolated
Stainless bolted to aluminium cold plates through a conductive fluid is a battery, and the aluminium loses. That is a loop-design question, and we raise it at enquiry rather than let the hose be blamed for it later.
Fire behaviour
A stainless hose and manifold add no combustible mass to the white space. That matters to the fire consultant and to the insurer before it matters to anyone else.
Tested before it ships
Every assembly is 100% pneumatically leak-tested and leaves with its certificate; hydrostatic proof to 1.5 × working pressure on request; manifolds and skids are tested as a unit. A leak found in our test bay is a line on a report; found in a rack, it is a claim.
Specification we build to
| Item | Standard build | Options |
|---|---|---|
| Hose | 316L annular corrugated to ISO 10380, single 316L braid | Double braid where the specification asks for it; PTFE-lined for dielectric or two-phase fluids on application |
| Hose ends | UQD-ready thread (BSPP, NPT, SAE ORB), or the coupling fitted; flanges to DIN PN6–PN40 or ANSI 150# at the CDU | Grooved-coupling-ready pipe ends, sanitary clamp ends, weld ends |
| Manifolds | 304L or 316L pipe, TIG-welded branches at the rack pitch, threaded ports, isolation and drain points | Pickled and passivated, or bright-annealed tube, where specified; brackets and rack-mounting hardware to drawing |
| Coolant | Water and PG25 propylene glycol — compatible with 316L and EPDM seals | Ethylene glycol, dielectric fluids and other coolants confirmed at enquiry |
| Temperature class | ASHRAE W17 to W45 supply classes; small derating applies (factor about 0.89 at 45 °C, 316L) | W+ (above 45 °C) — still far inside the hose range; the coupling seal sets the limit |
| Pressure | Working pressure set by the coupling (10 bar for UQD); hose margin stated on the drawing | Higher-pressure loops on flanged or threaded ends, to the published table |
| Cleanliness and dispatch | Assemblies internally flushed, dried, capped and bagged; manifolds capped at every port | Cleanliness protocol, fill fluid and labelling agreed at order where the OEM specifies them |
| Test and documents | Pneumatic leak test on every assembly and manifold; hydrostatic test and certificate per piece on request; wetted materials listed | EN 10204 3.1 mill certificates on request; third-party inspection with agreed hold points |
Materials follow the wetted-materials guidance the OCP liquid-cooling community publishes — stainless, copper alloys and EPDM in the same loop, aluminium kept out of it or isolated — and the coupling interface follows the OCP UQD specification, so a whip we build mates with any compliant coupling on the server side.
Who buys it, and how
CDU and rack OEMs
Whips, manifolds and CDU connections built to your drawing and your coupling family, in production quantities, with the per-piece certificate in the format your quality system files. We qualify on a sample first and plan for that sequence.
MEP and cooling contractors
The secondary loop from the CDU to the rack as one supply — hose kits by row, manifolds by rack, expansion joints on the plant — with a drawing for the consultant before the price.
Colocation and hyperscale operators
Replacement whips and manifolds to match what is installed, and the SFN for a new hall to the standard the first hall set. Send the coupling family and the rack layout; we do the rest.
India's data-centre clusters — Navi Mumbai and Mumbai, Hyderabad, Chennai, Pune, Noida and Bengaluru — are a day's road freight from Ahmedabad. For the Gulf, the network ships Ex Works Ahmedabad or FOB Mundra / Nhava Sheva to Jebel Ali, Dammam or Hamad Port; see the UAE and Saudi Arabia pages for how each market buys.
What to send for a quotation
Rack count and kW per rack ASHRAE W-class or supply temperature Coolant Coupling family and size at each end Manifold port count and pitch Rack layout or installed geometry CDU connection size and type Quantity, and kit or skid Test and documentation required
You get back a drawing of the network — hose lengths, manifold ports, coupling positions — and a specification first, then a price once the specification is settled. The lead time is stated on the quotation. Phone or WhatsApp +91 90815 68688 or +91 99259 57579, email info@essemworks.com, or the enquiry form.
Questions we are asked
What is a secondary fluid network in a data centre?
The closed coolant loop between the coolant distribution unit (CDU) and the IT equipment — supply and return pipework, row manifolds, rack manifolds and the flexible whips that connect each server's cold plates through quick-disconnect couplings. ASHRAE calls it the technology cooling system; the CDU separates it from the facility water loop that runs to the chillers.
Do you supply the UQD quick-disconnect couplings with the hoses?
Yes. We fit couplings to the OCP Universal Quick Disconnect interface — UQD02 to UQD08, and blind-mate UQDB where the rack design uses it — in the brand the CDU or server OEM has qualified, and test the assembly with the coupling on. The hose and the manifold are made in our works; the coupling is supplied to the specification.
Which stainless grade should an SFN hose be — 304L or 316L?
316L. Cooling water picks up chlorides from make-up water and inhibitor packages, and warm chloride-bearing water is the classic stress-corrosion condition for 304L. We build the secondary fluid network in 316L as standard, and the media compatibility page sets out where the chemistry needs more than that.
Can you fabricate rack manifolds and row manifolds to our drawing?
Yes — 304L or 316L, TIG-welded branches at the rack's pitch, ports threaded to the coupling standard, isolation and drain points, pressure tested and certified as a unit, with brackets and mounting hardware to the drawing.
Do you supply complete SFN skids?
We assemble the row manifold, valves, instruments and drain and vent points on a stainless frame, test the pipework as a unit and deliver it ready to connect to the CDU. The CDU and its pumps come from the OEM; the skid is built around their connections.
What pressure and temperature is an SFN hose assembly rated for?
Far above the duty. A DN25 single-braid 316L assembly carries 50 kg/cm² at 20 °C on our published ISO 10380 table, and the hose is rated from −196 to +450 °C, so the ASHRAE W17 to W45 supply classes need no derating. The quick-disconnect coupling, at 10 bar maximum working pressure, is the limiting element, and the drawing says so.
Related
Data-centre cooling hose
What the duty does to a hose, what we fit, what we would not, and what we need to size it.
View →Data centres
CDU connections, rack manifolds, chiller plant — the applications and the products that suit them.
View →SS braided corrugated hose
DN6 to DN350 — construction, the full pressure and bend-radius table, materials and standards.
View →